8BVI0014HWD0.000-1 B&R Inverter Module - Supplier in China

Products Mode: 8BVI0014HWD0.000-1
Place of Origin: AT

Inquery Now
Description
8BVI0014HWD0.000-1 B&R Inverter Module 
 
MATERIAL NUMBER:
8BVI0014HWD0.000-1
DESCRIPTION:
  • Uncontrolled stops and safe stop integrated
  • Integrated connection for motor motor holding brake and temperature sensor
  • 2 slots for ACOPOSmulti plug-in modules
  • Double axis modules contain two complete standalone inverters in an inverter module
ACOPOSmulti inverter module, 1.9 A, AS, wall mounting, 2 axes
General information
B&R ID code 0x26DF
Cooling and mounting type Wall mounting
Slots for plug-in modules 2
Certifications  
CE Yes
Functional safety Yes
UL cULus E225616
Power conversion equipment
EAC Yes
KC Yes
DC bus connection
Voltage  
Nominal 750 VDC
Continuous power consumption  2.91 kW
Power dissipation depending on switching frequency   
Switching frequency 5 kHz [1.2 * IM² + 2.62 * IM + 100] W
Switching frequency 10 kHz [2.56 * IM² + 2.8 * IM + 200] W
Switching frequency 20 kHz [6 * IM² - 9.4 * IM + 430] W
DC bus capacitance 165 µF
Variant ACOPOSmulti backplane
24 VDC power supply
Input voltage 25 VDC ±1.6%
Input capacitance 23.5 µF
Max. power consumption 16 W + PSLOT1 + PSLOT2 + P24 V Out + PHoldingBrake(s) 
Variant ACOPOSmulti backplane
24 VDC output
Quantity 2
Output voltage  
DC bus voltage (UDC): 260 to 315 VDC 25 VDC * (UDC/315)
DC bus voltage (UDC): 315 to 800 VDC 24 VDC ±6%
Fuse protection 250 mA (slow-blow) electronic, automatic reset
Motor connection
Quantity 2
Continuous power per motor connection  1.4 kW
Continuous current per motor connection  1.9 Aeff
Reduction of continuous current depending on switching frequency   
Switching frequency 5 kHz No reduction
Switching frequency 10 kHz No reduction
Switching frequency 20 kHz 0.11 A/K (starting at 15°C) 
Reduction of continuous current depending on installation elevation  
Starting at 500 m above sea level 0.19 Aeff per 1000 m
Peak current per motor connection 4.7 Aeff
Nominal switching frequency 5 kHz
Possible switching frequencies  5 / 10 / 20 kHz
Insulation stress of the connected motor per IEC TS 60034-25:2004  Limit value curve A 
Protective measures  
Overload protection Yes
Short-circuit and ground fault protection Yes
Max. output frequency 598 Hz 
Variant  
U, V, W, PE Connector
Shield connection Yes
Terminal connection cross section  
Flexible and fine-stranded wires  
With wire end sleeves 0.25 to 6 mm²
Approbation data  
UL/C-UL-US 30 to 10 AWG
CSA 28 to 10 AWG
Terminal cable cross section dimension of shield connection 12 to 22 mm
Max. motor line length depending on switching frequency  
Switching frequency 5 kHz 25 m
Switching frequency 10 kHz 25 m
Switching frequency 20 kHz 10 m
Motor holding brake connection
Quantity 2
Output voltage  24 VDC +5.8% / -0% 
Continuous current 1.1 A
Max. internal resistance 0.5 Ω
Extinction potential Approx. 30 V
Max. extinction energy per switching operation 1.5 Ws
Max. switching frequency 0.5 Hz
Protective measures  
Overload and short-circuit protection Yes
Open-circuit monitoring Yes
Undervoltage monitoring Yes
Response threshold for open-circuit monitoring Approx. 0.25 A
Response threshold for undervoltage monitoring 24 VDC +0% / -4%
Enable inputs
Quantity 4 (2 per axis)
Circuit Sink
Electrical isolation  
Input - Inverter module Yes
Input - Input Yes
Input voltage  
Nominal 24 VDC
Maximum 30 VDC
Input current at nominal voltage Approx. 30 mA
Switching threshold  
Low <5 V
High >15 V
Switching delay at nominal input voltage  
Enable 1 → 0, PWM off Max. 20.5 ms
Enable 0 → 1, ready for PWM Max. 100 µs
Modulation compared to ground potential Max. ±38 V
OSSD signal connections  Permitted
Max. test pulse length: 500 µs
Trigger inputs
Quantity 2
Circuit Sink
Electrical isolation  
Input - Inverter module Yes
Input - Input Yes
Input voltage  
Nominal 24 VDC
Maximum 30 VDC
Switching threshold  
Low <5 V
High >15 V
Input current at nominal voltage Approx. 10 mA
Switching delay  
Rising edge 52 µs ±0.5 µs (digitally filtered)
Falling edge 53 µs ±0.5 µs (digitally filtered)
Modulation compared to ground potential Max. ±38 V
Electrical properties
Discharge capacitance 0.2 µF
Operating conditions
Permissible mounting orientations  
Hanging vertically Yes
Horizontal, face up Yes
Standing horizontally No
Installation elevation above sea level  
Nominal 0 to 500 m
Maximum  4000 m
Pollution degree per EN 61800-5-1 2 (non-conductive pollution)
Overvoltage category per EN 61800-5-1 III
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature  
Operation  
Nominal 5 to 40°C
Maximum 55°C
Storage -25 to 55°C
Transport -25 to 70°C
Relative humidity  
Operation 5 to 85%
Storage 5 to 95%
Transport Max. 95% at 40°C
Mechanical properties
Dimensions   
Width 53 mm
Height 317 mm
Depth  
Wall mounting 263 mm
Weight Approx. 2.8 kg
Module width 1